FIXME **This page is not fully translated, yet. Please help completing the translation.**\\ //(remove this paragraph once the translation is finished)// {{indexmenu_n>1}} ====== Variant "Read" a) Read product data (basis product ID) ====== |<70% 20% 10% 45% 15%>| |^Variable ^Data type ^Description ^Direction| |Read* |BOOL |This variable sets PLC when new data is available and PLC sets it back to FALSE |From PLC to MES| |Read* |BOOL |This variable describes MES with TRUE, if the data was stored in the database. MES resets it to FALSE |From MES to PLC| |Product ID* |STRING |The generated database GUID is passed from PLC to MES, so that the measured values can be assigned faster |From PLC to MES| |Product Code* |STRING |The generated product code is provided by MES to PLC |From MES to PLC| |Product* |STRING |The product is provided by MES to the PLC |From MES to PLC| |Measured value 1..N |miscellaneous |The measured values or states of the produced part can be evaluated by the PLC in various data formats |From MES to PLC| {{:de:mes-schnittstellen:mes-datacollector:pde:lesen:lesen-a:pasted:20220520-121143.png}} * Section 1: * //{Product ID}// is set by PLC at least 300ms before //{Read}//. * Section 2: * //{Read}// is set by PLC * Section 3: * //{product code}// is set by MES * //{Product}// is set by MES * //{measured values 1..N}// are optionally set by MES * Section 4: * //{Read}// is set by MES. * Section 5: * //{Read}// is reset by PLC (**Reason**: rising edge //{Read}//). * //{Product ID}// is reset by PLC (**Reason**: rising edge //{Read}//). * Section 6: * //{Read}// is reset by MES (**Reason**: falling edge of //{Read}//) * //{Product code}// is reset by MES (**Reason**: falling edge of //{Read}//) * //{Product}// is reset by MES (**Reason**: falling edge of //{Read}//) * //{Measured values 1..N }// are reset by MES (**Reason**: falling edge of //{Read}//)